Coal mills, silos, and dust-handling equipment are constant fire risks. Our systems use CO2, Nitrogen, or Inert Gas to automatically prevent and control fires.

CO2 Inertisation Systems

High & Low Pressure CO2 systems for coal mills and silos.

Fully automated fire suppression systems designed to NFPA 12 standards. Available in high-pressure cylinder batteries or low-pressure refrigerated tank configurations.

High Pressure: Stored at 60 kg/cm²
Low Pressure: Stored at 300 psi (-18°C)
Fully automated with BMS integration
Automatic purging on high temp/CO signals
Non-conducting and safe for electrical systems

Technical Specifications

ComplianceNFPA 12 Guidelines
System TypeTotal Flooding / Local Application
ActivationAutomatic / Semi-Automatic / Manual
MonitoringContinuous weight/level monitoring

PSA Nitrogen Generator Systems

On-site nitrogen generation for continuous inerting.

Generate nitrogen on-site from atmospheric air using Pressure Swing Adsorption (PSA) technology. Eliminates cylinder dependency and logistics.

Carbon Molecular Sieves from Japan Enviro Chemicals
Purity from 99% to 99.99%
Skid-mounted compact unit
Low power consumption

Technical Specifications

Capacity5 Nm³/hr to 2,000 Nm³/hr
Purity99% - 99.99%
Dew Point-60°C NTP
PressureCustomisable

Inert Gas Generator Systems

Independent inert gas generation for remote locations.

Ideal for remote locations where CO2 refilling is impractical. Generates inert gas (CO2 + Nitrogen) through stoichiometric combustion of fuel.

Eliminates external gas supply dependency
Low capital and utility cost vs CO2
Automatic/Semi-automatic operation
Oxygen content < 1%

Technical Specifications

Capacity50 - 500 NM³/hr
Oxygen Content1%
CO Content< 200 PPM
FuelLiquid or Gaseous